How Many Exhaust Fans and Cooling Pads Does H-Type Layer Cage House Need?

H-Type Ventilation Sizing Worksheet

Fan quantity comes from required airflow. Cooling-pad area comes from the same airflow—not from bird number alone.

For an H-type layer cage house, the correct number of exhaust fans and the required cooling-pad area depend on house cross-section, target air velocity, actual fan performance at operating static pressure, cage density, inlet resistance and local temperature/humidity.

The calculation should therefore move in one direction: House → Air Velocity → Total Airflow → Fan Selection → Cooling Pad Area → Field Verification.

Direct Answer
Do not ask “How many fans for 30,000 layers?” first.

First calculate the airflow the building needs to achieve the selected hot-weather air speed. Then divide that airflow by the certified fan capacity at the expected static pressure. After fan airflow is established, size cooling-pad area from an acceptable pad-face velocity.

Three Core Equations
1. Required Airflow = Effective House Cross-Section × Target Air Velocity
2. Fan Quantity = Required Airflow ÷ Fan Airflow at Operating Static Pressure
3. Cooling Pad Area = Required Airflow ÷ Design Pad-Face Velocity
Keep units consistent. Final design must be checked against the actual fan curve, cooling-pad manufacturer data, static pressure and the completed H-type cage layout.

Read this page as the calculation chapter of the main guide: How to Design Ventilation for H-Type Layer Cage House in Hot Climates. The parent page explains airflow strategy and heat-stress management; this page focuses on fan and cooling-pad sizing.

01 · Collect the Inputs Before Calculating

What information is needed to calculate fans and cooling pads?

Fan quantity is a result of the completed house and layer cage design. Missing one of the following inputs can make a neat-looking calculation unreliable.

Input Why it matters
House width & effective height Together they define the effective air-moving cross-section used in the screening calculation.
House length Affects pressure loss, tunnel performance and the time air spends moving through the house.
H-type rows & tiers Change bird heat load and airflow resistance through the occupied cage zone.
Target hot-weather air speed Turns cross-sectional area into required airflow.
Fan curve / certified airflow Fan airflow falls as static pressure increases; nominal fan diameter is not enough.
Cooling-pad specification Pad thickness, material and manufacturer design velocity determine required area.
Peak temperature & RH Determine whether evaporative cooling is useful and how aggressively it should operate.

02 · Step 1 — Calculate Required Airflow

How does house size become an airflow requirement?

SI Formula
Q (m³/s) = A (m²) × V (m/s)
For m³/h: Q = A × V × 3,600

A is the effective cross-sectional area through which tunnel air must move. V is the selected target average air velocity for the design condition.

Heat-stress reference: Hy-Line’s current heat-stress technical guidance recommends increasing air movement in cages and cites about 1.8–2.0 m/s minimum in bird areas during danger-level heat-stress conditions. This is a bird-management reference, not a universal tunnel-house design speed for every LIVI project.

03 · Step 2 — Convert Airflow Into Fan Quantity

Why should fan quantity use airflow at static pressure?

Because an exhaust fan does not move its free-air rating once it is pulling through cooling pads, inlets, shutters and a long poultry house. Static pressure reduces delivered airflow.

Correct Input

Fan airflow at expected operating static pressure

÷
Not Enough

“50-inch fan” or “1,400 mm fan” alone

Fan Quantity Formula
Number of Fans = Required Total Airflow ÷ Certified Airflow per Fan at Design Static Pressure

Round up to a whole fan, then check whether the design needs practical reserve capacity for dirty shutters/pads, belt wear, fan aging or extreme-weather operation. The reserve should be an engineering decision, not an arbitrary fixed percentage.

04 · Static Pressure Can Change the Answer

What raises static pressure in an H-type layer house?

Cooling padsWet or dirty pads increase resistance compared with an open inlet. Inlet restrictionUndersized doors, curtains or openings can limit airflow. Fan accessoriesShutters, guards and cones affect delivered airflow.
House leakageUncontrolled air can bypass the intended cooling-pad path. Cage / equipment layoutRows, tiers and equipment can affect distribution through the occupied zone. Maintenance conditionDust, slipping belts and damaged shutters reduce real fan performance.

Mississippi State Extension recommends selecting poultry fans from independently rated performance data at relevant static pressure rather than free-air capacity. This is especially important once cooling pads and shutters are part of the system.

05 · Step 3 — Calculate Cooling-Pad Area

How much evaporative cooling-pad area is needed?

Once the fan system’s design airflow is known, calculate pad area from the allowable air speed through the selected pad.

Pad Area Formula
Cooling Pad Area = Total Design Airflow ÷ Design Pad-Face Velocity

Mississippi State Extension describes around 350 ft/min (about 1.78 m/s) as a typical design velocity for air entering evaporative pads, while also noting that actual pad velocities can vary considerably by system. Use the pad manufacturer’s specification for final design.

Important: increasing fan capacity without enough pad or tunnel-inlet area can increase static pressure and reduce the airflow gain you expected. Fans, pad area and inlet opening must be checked as one system.

06 · Illustrative Screening Calculation

What does the calculation look like in practice?

The example below is deliberately hypothetical. It shows the arithmetic only; it is not a LIVI quotation or a final ventilation design.

Example input Illustrative value
Effective air-moving cross-section 60 m²
Screening target air velocity 2.0 m/s
Required airflow 60 × 2.0 × 3,600 = 432,000 m³/h
Example fan capacity at design static pressure 40,000 m³/h per fan
Basic arithmetic fan count 432,000 ÷ 40,000 = 10.8 → 11 fans minimum by arithmetic
Example pad-face velocity 1.78 m/s
Basic pad-area screening 120 m³/s ÷ 1.78 ≈ 67.4 m²
Before turning this screening result into equipment quantities, an engineer must check the actual house geometry, H-type rows, pad/inlet arrangement, fan curves, operating static pressure, air leakage, local climate, cooling demand and reserve capacity.

07 · Why H-Type Layout Changes the Calculation Review

Do 4-tier and 5-tier layer cage houses use the same fan calculation?

The airflow equation is the same, but the engineering inputs and field verification can change. Higher tier count changes bird density, vertical heat distribution and airflow through the occupied cage zone.

4-Tier H-TypeCheck total bird load, cage-row resistance and air velocity across lower/middle/upper levels. 5-Tier H-TypeHigher vertical density increases the importance of clear height, upper-tier air movement and uniformity testing.

See 4-Tier vs 5-Tier H-Type Layer Cages for the broader layout decision. Also confirm the final number of rows using the H-type cage row calculation guide before the ventilation system is frozen.

08 · Cooling Pad Quantity Is Not Only an Area Question

How should the calculated pad area be arranged?

Check total net pad area. The gross wall opening and useful wet pad area are not always identical.
Check inlet opening behind/in front of the pad. Curtains, doors or framing must not become the real restriction.
Check pad height and available wall length. Required area must physically fit the house.
Check water distribution. Pads need uniform wetting, pump capacity and make-up water.
Check climate. Hot-dry climates benefit more from evaporative cooling than hot-humid conditions.

LIVI’s poultry environmental control system includes ventilation fans and cooling-pad equipment; final quantity should be tied to the project calculation rather than purchased as isolated accessories.

09 · Calculation Is Only Half the Job

What should be measured after the fans and pads are installed?

A correct spreadsheet can still produce poor bird-level conditions if installation or maintenance changes the real airflow.

✓ Full-tunnel static pressure ✓ Average house air speed
✓ Upper / middle / lower tier air movement ✓ Pad-end to fan-end temperature difference
✓ Uniform pad wetting ✓ Tunnel doors / inlets fully open
✓ Fan shutter and belt condition ✓ Uncontrolled air leakage
✓ Generator / alarm operation ✓ Re-test with birds stocked

10 · Five Sizing Mistakes

What causes fan and cooling-pad calculations to fail?

1. Dividing bird number by an arbitrary “birds per fan” rule.
2. Using free-air fan capacity instead of airflow at operating static pressure.
3. Adding fans without increasing restricted pad/inlet area.
4. Copying fan quantities from another H-type project with different house dimensions.
5. Never measuring actual air speed and static pressure after installation.

Ventilation Calculation Request

Send these data for a real fan / cooling-pad calculation

✓ Project country and city/region
✓ Peak summer temperature
✓ Peak / typical relative humidity
✓ House length × internal width × clear/effective height
✓ H-type cage model
✓ Number of rows
✓ 4-tier or 5-tier layout
✓ Total bird capacity per house
✓ Fan model or proposed fan performance data
✓ Cooling-pad specification
✓ Voltage / frequency
✓ Water source and backup power

Frequently Asked Questions

Exhaust fan and cooling-pad sizing questions

How many exhaust fans are needed for a 20,000- or 30,000-layer H-type house?
Bird capacity alone is not enough. Calculate required airflow from the effective cross-sectional area and target air speed, then divide by the selected fan’s certified airflow at the expected static pressure.

Can I calculate fan quantity from fan diameter?
No. Two fans with the same nominal diameter can deliver different airflow and efficiency, especially when static pressure rises.

What cooling-pad face velocity should I use?
Use the pad manufacturer’s engineering value. Around 350 ft/min (about 1.78 m/s) is a common published reference for evaporative pads, but it is not a universal value for every pad product.

Will adding more fans always increase house air speed?
Not proportionally. If pad area, inlet opening or other restrictions are too small, static pressure rises and each fan can deliver less airflow.

Should a 5-tier house automatically use more fans than a 4-tier house?
Not by a fixed fan-per-tier rule. Recalculate the completed house because bird density, cross-section, cage resistance and required bird-level air movement can all change.

Technical reference note: The calculation framework uses standard airflow relationships and current poultry engineering guidance. Heat-stress air-speed context is supported by Hy-Line International. Fan/static-pressure and evaporative-pad design principles are supported by U.S. university extension poultry ventilation publications. Final LIVI project values should always use the selected equipment’s engineering data.

Fan & Cooling Pad Calculation

Send the house and climate data

LIVI can coordinate the H-type cage layout, airflow requirement, fan selection and cooling-pad configuration for the project.